Our Products
RuckDemand Control Ventilation Commercial & Domestic FansIndustrial FansDuct Heaters & CoolersUnit Heaters & DehumidifiersAir Handling Units & Heat Recovery UnitsGrilles & DiffusersRoof HoodsChilled BeamsSpecialist Low Leakage DampersVolume, Fire & Smoke DampersFan Coils UnitsVAV's & CAV'sSilencersControllers

Volume, Fire & Smoke Dampers

DD Dampers

Volume Control Dampers

The DD Series Duct Balancing Damper was designed for duct installations to balance/regulate airflow.
All spindles revolve in low maintenance nylon bushes which are fitted within pressed inserts. Precise blade positioning is achieved via a robust dual-purpose quadrant and spindle assembly, operating the linkage mechanism which is located outside of the airstream.

The quadrant assembly is designed to facilitate simple conversion to motorisation without the need for additional components.
Features
Standard case construction is galvanised mild steel
Two airfoil blade designs
Four casing options
Out of airflow linkage
Easy conversion from manual to motorised or vice versa
Infinite sizing capability from 100 to 1000mm, 100 to 800mm dia.
Variable flange dimensions
Comprehensive control options
Can be supplied with blades and case in 316/430 stainless steel
Stainless steel side seals to order

Specifications & Tests
Unless stated otherwise, flange models are suitable for classes A & B of DW144 with spigot models suitable for classes A B & C of DW144
Conforms to HVCA specification DW144
Conforms to Eurovent 2/2 classes A - C
Independent performance tests for pressure drop, leakage and airtightness. Test reports 143, 145 and 146 refer


Blade Detail

leaf leaf

Plain Aluminium Blade with End Cap (left) or Galvanised Mild Steel or Stainless Steel Blade (right)

The 63mm wide extruded aluminium airfoil section blades are fitted to 12.5mm diameter spindles, with the option of galvanised mild steel or Grades 316 and 430 stainless steel blades available to order.

All models are available with either opposed or parallel blades (unless specified, opposed blades will be supplied as standard).
Fitted to the ends of the aluminium blades are End Caps to alleviate noise generation.